Gelişmiş Arama

Basit öğe kaydını göster

dc.contributor.authorKocabey, Süreyya
dc.contributor.authorEkren, Nazmi
dc.date.accessioned2021-12-12T17:01:22Z
dc.date.available2021-12-12T17:01:22Z
dc.date.issued2014
dc.identifier.issn0378-7788
dc.identifier.issn1872-6178
dc.identifier.urihttps://doi.org/10.1016/j.enbuild.2014.01.014
dc.identifier.urihttps://hdl.handle.net/20.500.11857/3167
dc.description.abstractThis paper presents a new approach for examination of insufficiency of a current lighting system and for performing maintenance plans of a lighting installation. Thus, a numerical algorithm based on finite element method (FEM) that ensures the required accuracy for illuminance calculations according to international lighting standards was developed. Experimental measurements were recorded in a controlled environment for the purpose of measuring the effectiveness of the algorithm. The average illuminance calculated according to CIBSE Code 1994 published by the Chartered Institution of Building Services Engineers (CIBSE) was obtained by error of 5.3% compared to the experimental measurements. Illuminance values of 894 points were calculated as 0.3% error according to the actual experimental measurements by proposed numerical algorithm that uses 36 pieces measurement data. Less experimental measurements provided more accurate results. The results obtained indicate that the suggested numerical model is very effective and usable in calculations of illuminance. In this way, this model will eliminate the requirement for long experimental measurements in lighting system controls that must be carried out periodically. (C) 2014 Elsevier B.V. All rights reserved.en_US
dc.language.isoengen_US
dc.publisherElsevier Science Saen_US
dc.relation.ispartofEnergy and Buildingsen_US
dc.identifier.doi10.1016/j.enbuild.2014.01.014
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectIlluminationen_US
dc.subjectIlluminanceen_US
dc.subjectFEMen_US
dc.subjectLighting system lifetimeen_US
dc.subjectLighting system maintenanceen_US
dc.titleA new approach for examination of performance of interior lighting systemsen_US
dc.typearticle
dc.authoridEkren, Nazmi/0000-0003-3530-9262
dc.departmentFakülteler, Mühendislik Fakültesi, Elektrik-Elektronik Mühendisliği Bölümü
dc.identifier.volume74en_US
dc.identifier.startpage1en_US
dc.identifier.endpage7en_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.authorscopusid23392496600
dc.authorscopusid24338101800
dc.identifier.wosWOS:000334817600001en_US
dc.identifier.scopus2-s2.0-84894289375en_US
dc.authorwosidkocabey, sureyya/AAA-5321-2021
dc.authorwosidEkren, Nazmi/AAA-3546-2019